A - specifications, General, Environmental – Rockwell Automation 1753-DNSI DeviceNet Safety Scanner for GuardPLC Controllers User Manual

Page 99: Appendix a, Specifications, Appendix, General environmental

Advertising
background image

1

Publication 1753-UM002A-EN-P - July 2005

Appendix

A

Specifications

General

Environmental

Dimensions
(H x W x D)

90 mm

(2)

x 110 mm x 87 mm

(3)

(3.5 in.

(2)

x 4.33 in. x 3.43 in.

(3)

)

(2) Height does not include DIN rail latches or mounting feet.

(3) Depth does not include communication cable.

Weight

400 kg (0.882 lb)

DeviceNet Current
Load, Max.

90 mA maximum @ 24V dc

Power Consumption

10 W maximum (on external power connection)

Response Overload

shut down of the concerned output with cyclic reconnecting

Isolation Voltage

30V continuous
Tested to withstand 500V dc for 60 seconds

HSP Cable

1753-CBLDN (ships with safety scanner)

Wire Type

Copper

Wiring Category

(1)

(1) Use this Conductor Category information for planning conductor routing. Refer to Industrial Automation Wiring

and Grounding Guidelines, publication number 1770-4.1.

2 - on power and communication ports

Storage Temperature

-40°C to +85°C (-40°F to +185°F)

Operating Temperature

0°C to +60°C (+32°F to +140°F)

Relative Humidity

IEC 60068-2-30
(Test Db, Un-packaged Non-operating Damp Heat):
5% to 95% noncondensing

Vibration

IEC60068-2-6 (Test Fc, Operating): 2g at 10 to 500 Hz

Operating Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock): 30g

Non-operating Shock

IEC60068-2-27 (Test Ea, Unpackaged Shock): 50g

Enclosure Type Rating

none (open-style)

Advertising