3 to 250 bytes – Rockwell Automation 1753-DNSI DeviceNet Safety Scanner for GuardPLC Controllers User Manual

Page 119

Advertising
background image

Publication 1753-UM002A-EN-P - July 2005

Calculate Safety Connection Bandwidth D-3

3 to 250 Bytes

In the equation below:

A = 1

÷ Data_RPI ÷ 0.001

B = (2 x Safety_Data_Size) + 8
C = (B

÷ 8) rounded to the nearest whole number

D = 1

÷ (Data_RPI x 100) ÷ 0.001

E = (B x 8 x bit_stuffing_factor) rounded to the nearest whole number

%Bandwidth =
100 x

(

{A x [(57 x C) + (B x 8) + E] +

2 x (D x 115 x Number_of_Consumers)}

÷ Baud_Rate

)

Advertising