Calculate Safety Connection Bandwidth D-3
3 to 250 Bytes
In the equation below:
A = 1
÷ Data_RPI ÷ 0.001
B = (2 x Safety_Data_Size) + 8
C = (B
÷ 8) rounded to the nearest whole number
D = 1
÷ (Data_RPI x 100) ÷ 0.001
E = (B x 8 x bit_stuffing_factor) rounded to the nearest whole number
%Bandwidth =
100 x
(
{A x [(57 x C) + (B x 8) + E] +
2 x (D x 115 x Number_of_Consumers)}
÷ Baud_Rate
)