Publication 1753-UM002A-EN-P - July 2005

Develop Your GuardPLC Application 8-5

4. Click the download icon and confirm the action by selecting Yes

to the warning prompt.

TIP

If this is the first time the application has been
downloaded, you may want to adjust the timing
parameters artificially high and allow the project to
run for several hours. This lets you gather statistics
on the system’s operation before refining the timing
parameters.

Set this parameter

Using

Controller Resend Timeout

RSLogix Guard PLUS! Hardware
Management

Controller Receive Timeout

Communications Time Slice

Watchdog Time

Safety Time

Scanner Receive Timeout

RSNetWorx for DeviceNet

Max. Scanner Response Time

Individual Safety/Standard
connection Timing parameters