Publication 1753-UM002A-EN-P - July 2005

Create a GuardPLC Project with High-Speed Safety Protocol 6-3

Add High-Speed Safety
Protocol to the GuardPLC
Controller Resource

To add High-Speed Safety Protocol (HSP) to your GuardPLC
controller:

1. Right-click on the Protocols folder under your Resource and

select New>HSP Protocol.

2. Configure HSP communications. Right-click on HSP Protocol

and select Properties.

The Controller Receive Timeout is the amount of time that the
controller waits to receive an HSP response from the scanner
before closing the HSP connection.

Controller Resend Timeout is the amount of time that the
controller waits for the acknowledgement of a message before it
resends it.