10-4 Monitor Status

Status Codes

S#ee

Status code for safety connections, where ‘ee’ is the decimal error code listed on page
10-4.

G#gg<:nnnn>

Extended error code for safety connections, where:

• ‘gg’ indicates the hexidecimal general status error code as listed in the Safety

Connection General Status Error Codes table on page 10-5, and

• ‘nnnn’ indicates the hexidecimal extended error code as listed in the table Safety

Connection Extended Error Codes on page 10-7.

E#ee

Status code for standard connections, where ee is the decimal error code listed in the
Status Codes table on page 10-4.

Display

Description

Status Code

(ee)

Description

Recommended Action

70

The address of the device is already in use by
another device on the network.

Change the address of the device to an unused address.

71

Illegal data in scan list.

Reconfigure the scan list and remove any illegal data.

72

No communication with the device.

Inspect the device and verify connections.

73

Device’s identity information does not match
electronic key in scanner

• Make sure that the correct device is at this address.
• Make sure that the device matches the specified electronic

key (vendor, product code, product type).

75

Either or both of the following:

• The device does not have a scan list.
• The device has not received

communication from any other device

Check that the device has:

• scan list
• properly wired connection to the network

76

No direct network traffic for scanner.

None. The scanner hears other network communication but does
not hear any directed to it.

77

During initialization, the data size expected by
the device does not match the scan list entry.

Check the device and the scan list for the correct input and output
size for the device.

78

Device is not communicating or communication
is intermittent.

• Check that the device has a properly wired connection to the

network.

• Check that the device has power.
• If the device is polled, make sure the interscan delay is long

enough for the device to return its data.

79

Scanner has failed to transmit a message.

• Make sure that your scanner is connected to a valid

network.

• Check for disconnected cables.

80

Scanner is in idle mode.

1. Put controller in run mode.

2. Make sure 1753-CBLDN is connected properly.

3. Make sure the scanner and the controller have the same

HSP signature.