Publication 1753-UM002A-EN-P - July 2005

8-4 Develop Your GuardPLC Application

Create Application Program
Logic

Create application program logic using the signals you defined.

Drag and drop the application signals, which are now connected
(mapped) to DeviceNet data signals, into the appropriate application
Type Instances and create your program logic.

Save and Compile
Application Logic

Save and compile your application logic.

Compiling the application logic and controller hardware configuration
results in a high-integrity computation of the HSP signature.

Refer to the GuardPLC Controller Systems User Manual, publication
number 1753-UM001, for details on creating, saving, and compiling
program logic.

Download the Project to the
Controller

Place the Controller in Stop Mode (if necessary)

Before you can download to the GuardPLC controller, the controller
must be in Stop mode. In RSLogix Guard PLUS! Hardware
Management, left-click on the stop icon on the Control Panel and
confirm the action by selecting Yes to the warning prompt.

Download the Project

In RSLogix Guard PLUS! Hardware Management:

1. Right-click on the controller resource.

2. Select Online > Control Panel.

3. Fill in your user name and password on the login screen. The

default username is Administrator with no password. Click OK.

TIP

Enter Ctrl-A to automatically fill in the default
username and access type.