Rockwell Automation 1753-DNSI DeviceNet Safety Scanner for GuardPLC Controllers User Manual
Page 65

Publication 1753-UM002A-EN-P - July 2005
Associate the Scanner and Controller and Download the DeviceNet Network Configuration 7-3
4. Select your RSLogix Guard PLUS! project.
a. If you have multiple RSLogix Guard PLUS! projects, use care
to select the correct one.
b. If you have multiple controller resources in your RSLogix
Guard PLUS! project, RSNetWorx prompts you to select the
correct resource.
5. RSNetWorx for DeviceNet automatically updates the Controller
ID and imports the Target Connections File from the associated
RSLogix Guard PLUS! project.
6. Click OK to establish the association.
Whenever the safety scanner configuration changes, RSNetWorx for
DeviceNet automatically generates or updates the Scanner Signals file.
TIP
Only RSLogix Guard PLUS! projects that
have at least one resource with HSP
communications enabled can be selected.
TIP
If RSLogix Guard PLUS! is open to the associated
project, then it automatically imports the Scanner
Signals file.