Plan your peer-to-peer communications, Commission a peer scanner – Rockwell Automation 1753-DNSI DeviceNet Safety Scanner for GuardPLC Controllers User Manual

Page 104

Advertising
background image

Publication 1753-UM002A-EN-P - July 2005

B-2 Configure Peer-to-Peer DeviceNet Communications

Plan Your Peer-to-Peer
Communications

If your application requires peer-to-peer DeviceNet communications,
you must:

• determine which RSLogix Guard PLUS! application signals each

controller and scanner combination needs to make available to
peer controllers, and

• determine whether the chosen signals should be made available

on standard or safety connections.

Only the following data types are supported:

The next steps are to set up your DeviceNet Network as discussed in
Chapter 3.

Commission a Peer
Scanner

1. Connect the scanner to the network following the installation

instructions in Chapter 2.

2. Commission the scanner, following the instructions in Chapter 3

to set the node address, baud rate, SNN, and password, if
desired.

The next step is to create a GuardPLC controller resource with HSP
protocol as described in Chapter 6.

Type

Size in
bits

Description

BOOL

1

true or false, on or off

USINT

8

unsigned byte

INT

16

signed word

UINT

16

unsigned word

DINT

32

signed double word

UDINT

32

unsigned double word

SINT

8

signed byte

REAL

32

float, IEC559 single precision format

LREAL

64

double, IEC559 double precision format

BYTE

8

string of 8 bits

WORD

16

string of 16 bits

DWORD

32

string of 32 bits