9-2 Verify Your DeviceNet Safety Configuration
appears listing those devices and their current status, including a
device icon overlaid with a status icon.
To return to RSNetWorx for DeviceNet so that you can correct the
status of the indicated devices, close the Safety Device Verification
Wizard by clicking on Cancel.
To skip the devices listed and continue the verification process for
other safety devices on the network, click Next.
Status
Icon
Overlay
Description
Missing
The device is part of the network configuration, but was
not found during the browse operation.
Mismatch
The device identity in the network configuration does
not match the identity of the online device.
Unknown
The device is in the configuration, but has not been
detected on the network yet.
Safety Network
Number Error
The Safety Network Number in the device is either
invalid or does not match the Safety Network Number
for the device in the RSNetWorx for DeviceNet
configuration file.
Signature
Mismatch
none
The configuration signature in the device does not
match the configuration signature in the RSNetWorx for
DeviceNet configuration file.
Safety Locked
The device is already locked.