1-8 Before You Begin

Communication Rate

The safety scanner supports the following communication rates, but
does not support autobaud:

• 125 Kbps (default)
• 250 Kbps
• 500 Kbps

Physical Layout of the
DeviceNet Safety System

Planning your system helps ensure that you can:

• meet safety times
• use memory and bandwidth efficiently
• fulfill device-specific requirements
• leave room for system expansion

Before configuring your 1753-DNSI scanner, you should be familiar
with each of the DeviceNet devices on your network. You should
know each device’s:

• system safety time requirements
• communication requirements
• I/O size
• frequency of message delivery

You must also understand and define which data elements can be
treated as safety and which as standard in your intended
configuration.

DeviceNet Safety I/O Performance Factors

Safety nodes have priority on a DeviceNet network, but the
performance of DeviceNet Safety I/O modules can be affected by the:

• baud rate of the network (Lower baud rates mean slower

transmissions and slower responses.)

• packet size for the various connections (Bigger packets may

result in fragmented messages and slower responses than
single-packet messages, but use fewer resources.)

• type and number of connections used (Using point-to-point

connections to make multiple connections to an input node uses
more resources than a multicast connection.)

• RPI of the devices (Lower RPIs consume more bandwidth but

lower system reaction time.)