Chapter

10

Monitor Status

To assist you in monitoring the status of devices on the DeviceNet
Safety network, the DeviceNet Safety Scanner provides:

• LED status indicators
• an alphanumeric status display.

You can also monitor the status of HSP, DeviceNet Safety and standard
connections, and the DeviceNet interface via connection status bits
and the corresponding GuardPLC application signals.

LED Status Indicators

The scanner has 3 LEDs which allow you to monitor module,
DeviceNet network, and High Speed Protocol (HSP) status.

LED

Color/State

Description

Module
Status

Off

No power.

Green, On

Operating under normal conditions.

Green, Flashing

Device is Idle.

Red, Flashing

A recoverable fault exists.

Red, On

An unrecoverable fault exists.

Red/Green, Flashing

Self-tests in progress or the device needs
commissioning due to configuration or unique node
identifier missing, incomplete, or incorrect.

Network
Status

Off

Device is not online or may not have DeviceNet network
power.

Green, On

Device is online; one or more connections are
established.

Green, Flashing

Device is online; no connections established.

Red, Flashing

Communication timeout.

Red, On

Communication failure. The device has detected an
error which has prevented network communication.

Red/Green, Flashing

The SNN is being set.