Rockwell Automation 1753-DNSI DeviceNet Safety Scanner for GuardPLC Controllers User Manual

Page 89

Advertising
background image

Publication 1753-UM002A-EN-P - July 2005

Monitor Status 10-5

Safety Connection General Status Error Codes

82

Error detected in sequence of fragmented I/O
messages from device.

• Check scan list device to make sure that its input and output

data sizes are correct.

• Check the configuration of the device.

83

Device returns error responses when the
scanner attempts to communicate with it.

• Check the accuracy of the scan list.
• Check the configuration of the device. The device may be in

another scanner’s scan list.

• Cycle power to the device.

84

Scanner is initializing the DeviceNet network.

None. This code clears itself once the scanner attempts to initialize
all the devices on the network.

85

During runtime, the device is sending the wrong
size of data.

Contact Rockwell Automation support. See the back of this
publication.

86

Device is in idle state/mode (not producing
data) while the scanner is in run mode.

• Check the configuration and status of the device.
• If you set up an interlock between 2 scanners (controllers),

make sure both scanners are in run mode.

92

The DeviceNet cable is not supplying power to
the communication port.

• Make sure the network has 24V dc power.
• Check the connection to the device.

95

The firmware of the device is currently being
updated.

None. Do not disconnect the device while the update is in progress.
You will lose any existing data in the device’s memory.

Status Code

(ee)

Description

Recommended Action

General
Status
Error Code
(00gg)

Description

0001

Connection failure occurred. See the extended error codes on pages 10-7
to 10-8.

0002

Resources required for the requested services were unavailable.

0003

Invalid value.

0004

Internal Object Identifier syntax error. See the extended error codes on
pages 10-7 to 10-8.

0005

Destination unknown, class unsupported, instance undefined, or structure
element undefined. See the extended error codes on pages 10-7 to 10-8.

0006

Packet space is insufficient.

0007

Connection was lost.

0008

Service is unsupported.

0009

An error occurred in a data segment or an attribute value is invalid.

000A

Attribute list error occurred.

000B

This state already exists.

000C

Object state conflict occurred.

000D

This object already exists.

000E

Attribute is not settable.

Advertising