Mount the scanner, Preventing electrostatic discharge -2, Mount the scanner -2 – Rockwell Automation 1753-DNSI DeviceNet Safety Scanner for GuardPLC Controllers User Manual

Page 22: Preventing electrostatic discharge

Advertising
background image

Publication 1753-UM002A-EN-P - July 2005

2-2 Install the 1753-DNSI

Preventing Electrostatic Discharge

Mount the Scanner

ATTENTION

Protective Debris Strip

Do not remove the protective debris strip until after
the module and all other equipment in the panel
near the module is mounted and wiring is complete.

Once wiring is complete, remove the protective
debris strip. Failure to remove the strip before
operating can cause overheating.

ATTENTION

This equipment is sensitive to electrostatic discharge,
which can cause internal damage and affect normal
operation. Follow these guidelines when you handle
this equipment:

• Touch a grounded object to discharge potential

static.

• Wear an approved grounding wrist-strap.
• Do not touch connectors or pins on component

boards.

• Do not touch circuit components inside the

equipment.

• If available, use a static-safe workstation.
• When not in use, store the equipment in

appropriate static-safe packaging.

IMPORTANT

For effective cooling:

• Because of thermal considerations, mount the

module horizontally only.

• Provide a gap of at least 100 mm (3.94 in.) above,

below, and on each side of the module.

• Provide a gap of at least 51 mm (2.0 in.) from the

front face of the module to the door of the
enclosure.

• Select a location where air flows freely or use an

additional fan.

• Do not mount the module over a heating device.

Advertising