16 bit bcd, 16 bit hex (hexadecimal) – Rockwell Automation 2707-NP2 MICROVIEW SOFTWARE PROGRAMMING MANUAL User Manual

Page 127

Advertising
background image

Publication 2707-PM002B-EN-P

MicroLogix Data Formats D-3

16 Bit BCD

This data format displays a 16 bit register address as a 4 digit Binary
Coded Decimal value.

16 Bit HEX (Hexadecimal)

This data format displays two consecutive 16 bit register addresses as
a 32 bit Hex value. It uses a memory register plus the next higher
register to form the 32 bit address.

TIP

The range for the 16 bit BCD selection is 0 to +9999.
This data format may also be scaled to different
engineering units.

Digit 1

Digit 2

Digit 3

Digit 4

Bit
16

Bit
13

Bit

12

9

Bit

8

Bit

5

Bit

4

Bit

1

Bit

Range = 0 to +9999

TIP

The range for the 32 bit HEX value is 0 to FFFFFFFF.
This format can’t be scaled to different engineering
units. Use this data format for display-only
(non-entry) operations.

Digit 1

Digit 2

Digit 3

Digit 4

Bit
16

Bit
13

Bit

12

9

Bit

8

Bit

5

Bit

4

Bit

1

Bit

Range = 0 to FFFF