Advisor update rate – Rockwell Automation 2707-NP2 MICROVIEW SOFTWARE PROGRAMMING MANUAL User Manual

Page 90

Advertising
background image

Publication 2707-PM002B-EN-P

12-12 Entering MicroView Configuration Data

Advisor Update Rate

Selecting Advisor Update Rate from the PLC Hardware Parameters –
Option Selection menu, displays the following:

The Advisor Update Rate is the periodic rate at which the MicroView
scans the Advisor register. For example a rate of 2.00 means the
MicroView reads the advisor register once every 2 seconds.

To assign a new Advisor Update Rate, enter a valid decimal number
and press [Return]. The valid range is from 1 to 12.5 seconds. The
default is 2 seconds. Entries are rounded up to the next higher 0.1
second.

To save the new Advisor Update Rate, press [Esc]. You are returned to
the PLC Hardware Parameter - Option Selection menu.

Note: Because the advisor adds to the network communication
traffic, the rate should be set to the highest possible value that is
acceptable for your application.