Chapter 14

Entering DTAM Configuration Data

14–11

When using AB DH485 or AB BASIC protocols, you must specify the
operating parameters that allow the DTAM Plus or DTAM Micro to
communicate with the SLC controller. The DTAM settings must match the
settings of the SLC or DH-485 network. If you are communicating with a
PLC-5, refer to the next section PLC Hardware Parameters.

When you select SLC Hardware Parameters from the DPS Configuration -
Option Selection menu, the following is displayed:

DTAM Plus
Only

Applies to:

Hardware

Parameter

DTAM

Plus

DTAM

Micro

Purpose

Com Port Setup

Defines the baud rate, parity, and number of
data bits used for communication with an
SLC or DH-485 network.

SLC 500 Slot Configuration

Specifies the number of inputs and outputs
in each controller slot. This allows the
DTAM to access the correct input and output
bit files.

Max Node Address

Sets the maximum node address on a
DH-485 network.

SLC 500 Node Address

Sets the node address of the SLC that the
DTAM is communicating with.

DTAM Node Address

Sets the address of the DTAM.

Downgrade File

Allows DTAM Plus files to be downgraded to
a Spectrum Controls format.

Advisor Update Rate

Sets the rate at which the DTAM reads the
advisor register.