Data Formats

The data selected for a controller address must reflect the same format as the
data actually stored in that address. This is the only way you can ensure that
correct, consistent information is displayed.

For example, selecting 16 Bit Signed Integer format for address N7:10
displays data one way and selecting 16 Bit BCD format for the same address
displays data another way. It is important to understand each data format and
its characteristics.

The following table illustrates all data formats supported by PLC and SLC
controllers including the point types and ranges applicable to each format,
and whether the scaling may be used.

Data Format

PLC Register Range

Scaling

User Input Range

Bit

0,1

No

0, 1, Y, N

16 Bit Signed Integer

-32,768 to +32,767

Yes

-32,768 to +32,767

16 Bit Unsigned Integer

0 to +65,535

Yes

-32,768 to +32,767

16 Bit BCD

0 to 9999

Yes

-32,768 to +32,767 ➀

16 Bit Hex

0 to FFFF

No

NA

32 Bit Unsigned Integer

0 to +4,294,967,295

No

0 to +4,294,967,295

32 Bit BCD

0 to +99,999,999

No

0 to +99,999,999

32 Bit Hex

0 to FFFFFFFF

No

NA

ASCII

20 Characters, Max

No

NA

Floating Point ➁

±

1.175495E

-38

to

±

3.402823E

+38

Yes

±

1.175495E

-38

to

±

3.402823E

+38

➀ 16 Bit BCD is 0-9999 on an SLC, but data can be scaled to -32,768 to +32, 768.
➁ Not available on SLC controllers.

Data Formats