Dtam plus / dtam micro file types – Rockwell Automation 2707-NP DTAM Programming Software User Manual

Page 27

Advertising
background image

Chapter 3
Designing DTAM Plus and
DTAM Micro Applications

3–3

Both the DTAM Micro and DTAM Plus can read and write PLC and SLC
controller files. Refer to the following when designing applications.

PLC-5 File Types

File Type Supported By;

Integer

File Type

DTAM Plus

DTAM Micro

Read / Write

Identifier

File Number

Element

Integer

Sub-Element

Bit Number

Output

Yes

Yes

Read

O

0

0-277➀

NA

0-17➀

Input

Yes

Yes

Read➁

I

1

0-277➀

NA

0-17➀

Status

Yes

Yes

Read / Write

S

2

0-127

NA

0-15

Bit (Binary)

Yes

Yes

Read / Write

B

3-999

0-999

NA

0-15999

Timer

Yes

Yes

Read / Write

T

3-999

0-999

PRE, ACC

EN, TT, DN

Counter

Yes

Yes

Read / Write

C

3-999

0-99

PRE, ACC

CU, CD, DN.

OV, UN

Control

Yes

Yes

Read / Write

R

3-999

0-999

LEN, POS

EN, EU,

DN, EM, ER,

UL, IN, FD

Integer

Yes

Yes

Read / Write

N

3-999

0-999

NA

0-15

Floating Point

Yes

Yes (Limited)

Read / Write

F

3-999

0-999

NA

NA

ASCII

Yes

Yes

Read

A

3-999

0-999

NA

0-15

BCD

Yes

Yes

Read / Write

D

3-999

0-999

NA

0-15

Block
Transfer

Yes

No

Read / Write

BT

3-999

0-999

NA

NA

Message

Yes

Yes

Read

MG

3-999

0-584

ERR, RLEN,

DLEN,

DATA 90-51)

NR, TO,

EN, ST, DN,

ER, CO, EW,

SD, SE

PID

Yes

No

Read / Write

PD

3-999

NA

NA

NA

SFC

Yes

No

Read / Write

SC

3-999

NA

NA

NA

ASCII String

Yes

Yes

Read

ST

3-999

0-799

LEN, CHAR

0-15

➀ Octal format, all other values are decimal. ➁ Remote I/O allows the DTAM to write it’s own output words.

SLC File Types

File Type Supported By;

Integer

File Type

DTAM Plus

DTAM Micro

Read / Write

Identifier

File Number

Element

Integer

Sub-Element

Bit Number

Output

Yes

Yes

Read

O

0

0-255

NA

0-15

Input

Yes

Yes

Read

I

1

0-255

NA

0-15

Status

Yes

Yes

Read / Write

S

2

0-82

NA

0-15

Bit (Binary)

Yes

Yes

Read / Write

B

3, 9-255

0-255

NA

0-4094

Timer

Yes

Yes

Read / Write

T

4, 9-255

0-255

PRE, ACC

EN, TT, DN

Counter

Yes

Yes

Read / Write

C

5, 9-255

0-255

PRE, ACC

CU, CD, DN,

OV, UN

Control

Yes

Yes

Read / Write

R

6, 9-255

0-255

LEN, POS

EN, EU,

DN, EM, ER,

UL, IN, FD

Integer

Yes

Yes

Read / Write

N

7, 9-255

0-255

NA

0-15

ASCII

Yes

Yes

Read

A

3-999

0-999

NA

0-15

ASCII String

Yes

Yes

Read

ST

3-999

0-799

LEN, CHAR

0-15

Floating Point

Yes

Yes

(Limited)

Read / Write

F

3-999

0-999

NA

NA

③ Need SLC 5/03 Series C w/OS 301 or SLC 5/04.

DTAM Plus /
DTAM Micro File Types