Chapter 8

Creating Data Entry Screens

8–7

16 Bit Signed Integer,
16 Bit Unsigned Integer,
16 Bit BCD (Binary Coded Decimal)

The screen for a 16 Bit Unsigned Integer format is shown below. The
screens for 16 Bit Signed Integer and 16 Bit BCD formats are similar.

SLC or PLC

depending upon protocol.

Format Selection

Description

Register Number

The controller data address to be monitored.

Digits Right of Decimal

The number of digits to be placed to the right of the decimal.

Digits Left of Decimal

The number of digits to be placed to the left of the decimal.

Leave Place for Sign (Y or N)

Provides for a one character place for the polarity sign (+ or -) when
the data is displayed, if desired.

Minimum Register Value

The minimum data value of the controller address being monitored.

Maximum Register Value

The maximum data value of the controller address being monitored.

Minimum Entry Value

The minimum data value to be entered. When this value is
entered the minimum register value is entered to the defined
controller address.

Maximum Entry Value

The maximum data value to be entered. When this value is entered
the maximum register value is entered to the defined controller
address. The range defined by the minimum entry value and the
maximum entry value is proportionally scaled to the range of the
minimum and maximum register values. If both ranges are equal
then the scaling ratio is 1:1.

Low User Input Limit

The minimum entry value that an operator may enter. This value
must be within the minimum and maximum entry values. If a value
lower than this limit is entered the DTAM will display an “Input Error”
screen displaying the minimum and maximum entry limits.

High User Input Limit

The maximum entry value that an operator may enter. This value
must be within the minimum and maximum entry values. If a value
higher than this limit is entered the DTAM will display an “Input Error”
screen displaying the minimum and maximum entry limits.

Default Value

This parameter defines a default value that is displayed at the entry
address of the display. An entry of Z defines no default value.
NONE appears in the window when Z is entered.