DTAM Plus ASCII Bar Code Input

This chapter describes how to input ASCII bar code data through the optional
printer port of the DTAM Plus.

Section

Page

Printer Form Builder

17–1

Printer Control

17–1

Print Form Builder Function Keys

17–2

Creating a Printer Form

17–3

Versions of the DTAM Plus with the optional printer port allow ASCII data
to be written to a data entry display. The ASCII data may be from a variety
of sources, including Allen-Bradley decoded bar code scanners:

Hand-Held Scanners (Catalog No. 2755-G3-D or -G6-D)

Fixed Mount Scanners (Catalog No. 2755-LD1-D or -LD2-D)

Allen-Bradley bar code scanners transmit data after a successful decode in
the following format:

Prefix Scanner ID Preamble Code ID Data Postamble Suffix

The DTAM Plus supports the following fields of the bar code message
format.

Field

Field Name

Contents

DTAM Plus Support

1

Prefix

STX

Only STX is supported.

2

Scanner ID

Two character ASCII identifier
form 01 to 99.

user can specify whether or
not the scanner ID field is
used by the DTAM.

3

Preamble

None

No preamble is supported.
This is the default setting of
the scanners.

4

Code ID

None

No code ID is supported. This
is the default setting of the
scanners.

5

Data

1 to 32 ASCII characters.

This field is variable and con-
tains the exact number of
characters scanned.

5

Postamble

None

No postamble is supported.
This is the default setting of
the scanners.

7

Suffix

CR LF

(Carriage Return / Line Feed)

CR LF is the default setting of
the scanners.

Chapter Objectives