background image

Chapter 14

Entering DTAM Configuration Data

14–20

All other programming and configuration for DTAM Plus/Micro DeviceNet
applications are the same as for other DTAM Plus/Micro products.

The DTAM Plus/Micro DeviceNet supports the following file types:

File Type

Description

Read/Write Access

I

Input

Read and Write

O

Output

Read Only

The number of Input and Output words is determined by the Input Buffer
Size and Output Buffer Size parameters.

Advisor Update Rate

Selecting Advisor Update Rate from the PLC Hardware Parameters - Option
Selection menu, displays the following:

The Advisor Update Rate is the periodic rate at which the DTAM scans the
Advisor register. For example a rate of 2.00 means the DTAM reads the
advisor register once every 2 seconds.

To assign a new Advisor Update Rate, enter a valid decimal number and
press [Return]. The valid range is from 1 to 12.5 seconds. The default is 2
seconds. Entries are rounded up to the next higher 0.1 second.

Note: Because the advisor adds to the network communication traffic, the
rate should be set to the highest possible value that is acceptable for your
application.

To save the new Advisor Update Rate, press [Esc]. You are returned to the
PLC Hardware Parameter - Option Selection menu.

PLC Hardware Parameters

Supported File Types