Devicenet connections – Rockwell Automation 2711-ND3 PanelBuilder32 Quick Start Manual User Manual
Page 21

Publication 2711-QS003D-EN-P - June 2009
21
System Setup Chapter 1
DeviceNet Connections
DeviceNet versions of the PanelView terminal have a DeviceNet
communication port and an RS-232 port for file transfers/printing.
Connect the PanelView terminal to a DeviceNet link using DeviceNet
cable, catalog number 1485C-P1A50, -P1A150, -P1A300. The
illustration shows an SLC or PLC controller. Another option would be
a ControlLogix controller with a 1756-DNB module.
1747-SDN DeviceNet
Scanner Module
Cable
Catalog No. 2711-NC13,
2711-NC14, 2706-NC13
Cable 1485C-P1A50, -P1A150, -P1A300
1771-SDN DeviceNet
Scanner Module
Requires 24 Volt
Power Supply
PLC-5 Controller
PanelView 1000 Terminal
SLC 5/03, /04, /05 Controller
5
1
DeviceNet Port
RS-232 Port
Serial Link
PanelBuilder32 Software
DeviceNet
Terminal Block
Terminal
Signal
Function Color
1
COM
Common
Black
2
CAN_L
Signal Low
Blue
3
SHIELD
Shield
Uninsulated
4
CAN_H
Signal High
White
5
VDC+
Power Supply
Red
1