Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual
Page 102
Advertising
![background image](/manuals/581226/102/background.png)
B-2
PROFIBUS Communications Module
Displays the port to which the module is connected. This will usually
be port 5.
Displays the data rate used by the drive. This data rate is set in the
drive and the module detects it. This will usually be 500 Kbps.
Sets the node address if the node address switches are set to “00.”
Displays the PROFIBUS node address actually used by the
module.
1
DPI Port
Range:
0 to 7
Default:
0
Type:
Read Only
Reset Required: N/A
2
DPI Data Rate
Range:
0 = 125 kbps
1 = 500 kbps
Default:
0 = 125 K
Type:
Read Only
Reset Required: N/A
3
P-DP Addr Cfg
Range:
00 to 126
Default:
01
Type:
Read/Write
Reset Required: Yes
4
P-DP Addr Actual
Range:
0 to 126
Default:
N/A
Type:
Read Only
Reset Required: N/A