Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 82

Advertising
background image

7-8

PROFIBUS Communications Module

Figure 7.5 – Reading Fault 1 Time (Parameter 244) from the SP600 Drive

(DPI Port 0)

Confirms Par. Access Word 2 of the request
(DPI Port #)

Message

1000 hex = Read

N20:10

Command

1

P

ar

. Access

W

ord

SLC Address

Descr

iption

Value (he

x)

N10:12

N20:13

N20:12

N20:11

N10:10

N10:13

Reply

3

2

2

1

4

4

3

DPI Port 0 (DPI Host)

Not Used

Not Used

Confirms Par. Number of the request ("F4")

Transferring 16-bit parameter value ("1")

Parameter value high word*1

F4 hex = 244 dec (parameter 244)

0

0

0

518E

1B

N10:11

0

Parameter value low word*1

*Note 1: 1B518E hex = 1,790,350 decimal equates to 179.0350
hours (fixed decimal point)

10F4

10F4