Configuring the PROFIBUS Module
4-5
4.5.1 Setting the Fault Configuration Parameters
If you set module parameter 9 (Comm Flt Action) or module
parameter 10 (Idle Flt Action) to “Send Flt Cfg,” the values in the
parameters shown in table 4.3 are sent to the drive after a
communications fault and/or idle fault occurs. You must set these
parameters to values required by your application.
Changes to these parameters take effect immediately. A reset is not
required.
Table 4.3 – Fault Configuration Parameters
Number
Name
Description
13
Flt Cfg Logic
A 16-bit value sent to the drive
for Logic Command
14
Flt Cfg Ref
A 32-bit value (0 to 4294967295)
sent to the drive as a Reference
or Datalink.
Important: If the drive uses a
16-bit Reference or 16-bit
Datalinks, the most significant
word of the value must be set to
zero (0) or a fault will occur.
15 - 22
Flt Cfg x1 In or
Flt Cfg x2 In