Troubleshooting the PROFIBUS Module and Network

8-7

8.3

Viewing and Clearing Events

The module maintains an event queue that reports the history of its
actions. You can view the event queue using an LCD OIM or
VS Utilities software.

To View and Clear Events Using an LCD OIM

Use the procedure shown in figure 8.2 to access the event queue
using the LCD OIM. Note that you must have the RECOMM-PBUS
module as the selected device to access the event queue.

Events

Many events in the event queue occur under normal operation. If
you encounter unexpected communications problems, the events
may help you or Reliance Electric personnel troubleshoot the
problem. Table 8.5 lists events that may appear in the event queue.

Figure 8.2 – Viewing and Clearing Events Using an LCD OIM

Diagnostics:

Device Version

OIM Version

View Event Queue

P0: RECOMM-PBUS

Stopped Auto

Main Menu

Diagnostics

EvtQ# : E#xxxxx
Online @ 500kbps

1

Clrqu

Highlight Diagnostics icon

Highlight item

Monitor

Lang

>>

Press F2 key to

clear event queue

Table 8.5 – Event Codes and Descriptions

Code

Event

Description

1

No Event

Empty event queue entry.

2

DPI Bus Off Flt

A bus-off condition was detected on DPI. This
event may be caused by loose or broken
cables or by noise.

3

Ping Time Flt

A ping message was not received on DPI
within the specified time.

4

Port ID Flt

The module is not connected to a correct port
on a DPI product.

5

Port Change Flt

The DPI port changed.

6

Host Sent Reset

The DPI product issued this because it was
reset.

7

EEPROM Sum Flt

The EEPROM in the module is corrupt.