5 setting a fault action – Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 28

Advertising
background image

4-4

PROFIBUS Communications Module

4.5

Setting a Fault Action

By default, when communications are disrupted (for example, a
cable is disconnected) or the master is idle, the drive responds by
faulting if it is using I/O from the network. You can configure a
different response to communication disruptions using module
parameter 9 (Comm Flt Action) and a different response to an idle
scanner using parameter 10 (Idle Flt Action).

Set the values of parameter 9 (Comm Flt Action) and parameter 10
(Idle Flt Action) to the desired responses as shown in table 4.2. See
figure 4.4 for sample LCD OIM Fault Action screens.

Changes to these parameters take effect immediately. A reset is not
required.

!

ATTENTION: Parameter 9 (Comm Flt Action) and
parameter 10 (Idle Flt Action) let you determine the
action of the module and connected drive if
communications are disrupted or the scanner is idle.
By default, these parameters fault the drive. You can
set these parameters so that the drive continues to
run. Precautions should be taken to ensure that the
settings of these parameters do not create a risk of
injury or equipment damage.

Table 4.2 – Selections for Drive Response to Communication Fault

Value

Action

Description

0

Fault (default)

The drive is faulted and stopped (Default).

1

Stop

The drive is stopped, but not faulted.

2

Zero Data

The drive is sent 0 for output data after a
communications disruption. This does not
command a stop.

3

Hold Last

The drive continues in its present state after a
communications disruption.

4

Send Flt Cfg

The drive is sent the data that you set in the
fault configuration parameters 13 through 22
(Flt Cfg Logic through Flt Cfg D2 In).

Figure 4.4 – Fault Action Screens on an LCD OIM

Port 5 Device

RECOMM-PBUS

Parameter #: 9
Comm Flt Action

0

Fault

Port 5 Device

RECOMM-PBUS

Parameter #: 10
Idle Flt Action

0

Fault

Advertising