Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 22

Advertising
background image

3-6

PROFIBUS Communications Module

Step 4.

For 1-20 HP SP600 drives, fold the Internal Interface
cable behind the module and mount the module on the
drive using the four captive screws. See figure 3.6.

For frame 2 and larger SP600 drives, mount the module

on the drive using the four captive screws to secure and
ground it to the drive.

Important: All screws must be tightened since the module is

grounded through a screw. The recommended
tightening torque is 0.9 N-m (8 in-lb).

Figure 3.6 – Mounting and Grounding the PROFIBUS Module

Module

Drive

Internal Interface cable
folded behind the module

and in front of the drive.

SP600 Drive

SP600 Drive

Frame 2 and Larger

1-20 HP