2 using the lcd oim to configure the module, 3 setting the node address – Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 26

Advertising
background image

4-2

PROFIBUS Communications Module

4.2

Using the LCD OIM to Configure the
Module

Use the procedure in figure 4.1 to access the parameters on the
PROFIBUS module using the LCD OIM. If you are unfamiliar with
the operation of the LCD OIM, refer to the SP600 AC Drive User
Manual (D2-3485 or D2-3501) for more information.

4.3

Setting the Node Address

If the node address switches are set to “00”, the value of module
parameter 3 (P-DP Addr Cfg) determines the node address.

Step 1.

Set the value of parameter 3 (P-DP Addr Cfg) to a unique
node address as shown in figure 4.2.

Step 2.

Reset the module. Refer to section 4.5.2, Resetting the
Module.

Figure 4.1 – Accessing the PROFIBUS Parameters Using the LCD OIM

P0: SP600

>>

Auto

Stopped

Main Menu

Device Select

Use to select

RECOMM-PBUS.

P0: SP600

>>

Auto

Stopped

P5: RECOMM-PBUS

>>

Auto

Stopped

Main Menu

Parameters

Device: Port 0

SP600

RECOMM-PBUS

Monitor

Lang

Edit the PROFIBUS
parameters using the
same techniques as for
drive parameters.

Use to highlight

Device Select icon

Figure 4.2 – PROFIBUS Node Address Screen on an LCD OIM

Port 5 Device

RECOMM-PBUS

Parameter #: 3
P-DP Addr Cfg

01

0 <> 126

Default = 01