PROFIBUS Communications Module
4.2
Using the LCD OIM to Configure the
Module
Use the procedure in figure 4.1 to access the parameters on the
PROFIBUS module using the LCD OIM. If you are unfamiliar with
the operation of the LCD OIM, refer to the SP600 AC Drive User
Manual (D2-3485 or D2-3501) for more information.
4.3
Setting the Node Address
If the node address switches are set to “00”, the value of module
parameter 3 (P-DP Addr Cfg) determines the node address.
Step 1.
Set the value of parameter 3 (P-DP Addr Cfg) to a unique
node address as shown in figure 4.2.
Step 2.
Reset the module. Refer to section 4.5.2, Resetting the
Module.
Figure 4.1 – Accessing the PROFIBUS Parameters Using the LCD OIM
P0: SP600
>>
Auto
Stopped
Main Menu
Device Select
Use to select
RECOMM-PBUS.
P0: SP600
>>
Auto
Stopped
P5: RECOMM-PBUS
>>
Auto
Stopped
Main Menu
Parameters
Device: Port 0
SP600
RECOMM-PBUS
Monitor
Lang
Edit the PROFIBUS
parameters using the
same techniques as for
drive parameters.
Use to highlight
Device Select icon
Figure 4.2 – PROFIBUS Node Address Screen on an LCD OIM
Port 5 Device
RECOMM-PBUS
Parameter #: 3
P-DP Addr Cfg
01
0 <> 126
Default = 01