Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 106

Advertising
background image

B-6

PROFIBUS Communications Module

Sets the I/O that the module is actively transmitting. The value of
this parameter will usually be equal to the value of DPI I/O Config
(parameter 11).

Sets the Logic Command data that is sent to the drive if the
following is true:

• Comm Flt Action (parameter 9) is set to Send Flt Cfg and

communications are disrupted.

• Idle Flt Action (parameter 10) is set to Send Flt Cfg and the

scanner is put into Program or Test mode.

The bit definitions will depend on the product to which the module is
connected.

12

DPI I/O Active

Range:

See figure B.2.

Default:

See figure B.2.

Type:

Read Only

Reset Required: N/A

Figure B.2 – DPI I/O Active (Parameter 12)

0

0

0

1

0

x

x

x

0

1

2

3

4

5

6

7

1 = I/O Enabled
0 = I/O Disabled
x =Not Used

Cmd/Ref

Datalink A

Datalink B

Datalink C

Datalink D

Not Used

Not Used

Not Used

13

Flt Cfg Logic

Range:

0000 0000 0000 0000 to 1111 1111 1111 1111

Default:

0000 0000 0000 0000

Type:

Read/Write

Reset Required: No

Advertising