3.3

Connecting the Module to the
Network

Step 1.

Remove power from the drive.

Step 2.

Use static control precautions.

Step 3.

Route the PROFIBUS cable through the bottom of the
SP600 drive. (See figure 3.6.)

Step 4.

Connect a PROFIBUS connector to the cable. (See
figures 3.2 and 3.3.)

Note: PROFIBUS connectors are available from a variety
of sources and in various sizes. As such, there may be
mechanical limitations that prohibit the use of some
connectors. Phoenix Subcon Plus M1 (Part # 2761826) or
ERNI PROFIBUS vertical (Node Part # 103658 and
Termination Part # 103659 connectors) are
recommended for use with SP600 and other Reliance
Electric DPI-based drives.

Setting

Description

00 - 99

Node address used by the module if switches are
enabled. The default switch setting is 05.

Important:If the address switch is set to “00”, the
module will use the setting of P-DP Addr Cfg
(module parameter 3) for the node address. Refer
to chapter 4, Configuring the PROFIBUS Module.

Figure 3.1 – Setting the Node Address

2

1

0

9

8

3

4

5

6

7

2

1

0

9

8

3

4

5

6

7

Tens

Ones

Digit

Digit

!

ATTENTION: The drive may contain high voltages
that can cause injury of death. Remove all power
from the drive, and then verify power has been
removed before installing or removing a PROFIBUS
module. Failure to observe these precautions could
result in severe bodily injury or loss of life.