Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual
Page 108
Advertising
B-8
PROFIBUS Communications Module
Sets the format used when performing explicit messages:
• Par Prot (Parameter Protocol) is used to read or write single
parameters.
• DPI Par Prot is reserved for future use.
Performing explicit messaging requires the “Parameter Access”
module to be added when configuring the node with a network
software tool.
Displays the state of the PROFIBUS controller.
23
Parameter Mode
Range:
0 = Par Prot
1 = DPI Par Prot
Default:
0 = Par Prot
Type:
Read/Write
Reset Required: No
24
P-DP State
Range:
0 = WAIT_PRM
1 = WAIT_CFG
2 = DATA_EX
3= ERROR
Default:
N/A
Type:
Read Only
Reset Required: N/A