8.1.3 NET A Status Indicator
Table 8.3 – NET A Status Indicator: State Definitions
Status
Cause
Corrective Actions
Off
The module is not
powered or is not
connected properly
to the network.
•
Securely connect the module to
the drive using the Internal
Interface cable and to the
network using a PROFIBUS
cable.
•
Correctly connect the
PROFIBUS cable to the
PROFIBUS connector.
•
Apply power to the drive.
Flashing
Red
Error in PROFIBUS
configuration.
•
Re-configure the PROFIBUS
module.
Solid
Red
Error in PROFIBUS
controller
initialization.
•
Cycle power to the drive.
•
Re-configure the PROFIBUS
scanner.
Solid
Green
The module is
properly connected
and communicating
on the network.
•
No action required.