PROFIBUS Module Parameters
B-7
Sets the Reference data that is sent to the drive if any of the
following is true:
• Comm Flt Action (parameter 9) is set to Send Flt Cfg and
communications are disrupted.
• Idle Flt Action (parameter 10) is set to Send Flt Cfg and the
scanner is put into Program mode.
Important: If the drive uses a 16-bit Reference, the most significant
word of this value must be set to zero (0) or a fault will
occur.
Sets the data that is sent to the Datalink in the drive if any of the
following is true:
• Comm Flt Action (parameter 9) is set to Send Flt Cfg and
communications are disrupted.
• Idle Flt Action (parameter 10) is set to Send Flt Cfg and the
scanner is put into Program mode.
14
Flt Cfg Ref
Range:
0 to 4294967295
Default:
0
Type:
Read/Write
Reset Required: No
15
16
17
18
19
20
21
22
Flt Cfg A1
Flt Cfg A2
Flt Cfg B1
Flt Cfg B2
Flt Cfg C1
Flt Cfg C2
Flt Cfg D1
Flt Cfg D2
Range:
0 to 4294967295
Default:
0
Type:
Read/Write
Reset Required: No