5-8
PROFIBUS Communications Module
Logic Command / Status, Reference / Feedback, Datalinks and
Parameter Access (explicit messaging) modules are added using
the Modules tab.
Step 10. Click on the Modules tab. Click Add to view the choice of
modules.
In our example, Station 1 will be controlled using Logic
Command / Status and Reference / Feedback. The
SP600 drive uses 16-bit Reference / Feedback (2 bytes).
Step 11. Select “Ctrl/Stat & Ref/Fdbk (2+2bytes)” from the
“Available Modules” list as shown in figure 5.13. Click OK.
Figure 5.12 – RECOMM-PBUS Modules Tab
Figure 5.13 – Available Modules: Ctrl/Stat & Ref/Fdbk (2x2Bytes) Window
Reliance Electric RECOMM-PBUS