PROFIBUS Communications Module

7.5

Sample SLC Ladder - Station 2
Parameter Protocol

Figure 7.11 – Sample SLC Ladder Logic - Station 2 Parameter Protocol (Continued)

This circuit utilizes the Parameter Protocol. A REQUEST to Station 2 is processed only one at a time, and after each
RESPONSE from Station 2 a zero must be sent and received to 'handshake' before the next REQUEST/RESPONSE transaction
can take place. For example:

Elsewhere in the user program these words must be loaded with message data prior to initiating the REQUEST:
N7:30 = RC = the operation to be performed ("1"=Read, "2" = 16-bit Write, "3" = 32-bit Write)
N7:31 = PNU = the parameter number to read or write
N7:32 = Subindex = the DPI port # ("0"= Host or SP600 drive, "5" = RECOMM-PBUS, etc.)
N7:33 = PVA #1 = the parameter value (high word) - only used when writing parameters
N7:34 = PVA #2 = the parameter value (low word) - only used when writing parameters

The four Parameter Protocol Words set up in the scanner are used to perform the Parameter Protocol:
N20:24 = contains RC (the operation to be performed) and PNU (the parameter number to read or write) combined
N20:25 = Subindex (the DPI port #)
N20:26 = PVA #1 (the parameter value (high word))
N20:27 = PVA #2 (the parameter value (low word))

Send a parameter read request --> Receive a parameter read response --> Send a "0" --> Receive a "0" --> [Transaction complete]

If the RESPONSE PCA Word 1 (N10:24) is "0", then a REQUEST can be initiated.


B3:19/0 is turned ON elsewhere in the program after the REQUEST message (N7:30-34) is loaded. This causes one Parameter
Protocol read or write to occur and B3:19/0 is turned OFF when the transaction is complete.

0016

B3:19

0

Station 2
Par Prot
Messaging
Request

EQU

Equal
Source A

N10:24

0<
Source B

0

0<

EQU

Station 2
RESPONSE
PCA Word

MOV

Move
Source

N7:31

9<
Dest

N20:24

0<

MOV

Station 2
PCA Word

N7:30

0

RC bit 0

L

N20:24

12

PCA Word
RC
bit 0

N7:30

1

RC bit 1

L

N20:24

13

PCA Word
RC
bit 2

COP

Copy File
Source

#N7:32

Dest

#N20:25

Length

3

COP

IND Word
(Subindex)

This section of the routine is only needed if the application needs to perform Parameter Protocol Reads or Writes to Station 2.

On power-up, initialize the Parameter Protocol routine.

0015

S:1

15

First Pass

U

B3:19

0

Station 2
Par Prot
Messaging
Request

Advertising