Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 64

Advertising
background image

6-12

PROFIBUS Communications Module

Figure 6.6 – Sample SLC Ladder Logic - Main Program (Continued)

Execute LAD 4 - Station 2 Drive Logic

0006

JSR

Jump To Subroutine
SBR File Number

U:4

JSR

The PROFIBUS scanner is configured for 28 bytes (14 words) of outputs for each drive. Two drives require 48 bytes (28 words).

Station 1

Station 2

Description

M0:1.0

(N20:0)

M0:1.14

(N20:14)

Logic Command

M0:1.1

(N20:1)

M0:1.15

(N20:15)

Speed Reference

M0:1.2

(N20:2)

M0:1.16

(N20:16)

Datalink A1

M0:1.3

(N20:3)

M0:1.17

(N20:17)

Datalink A2

M0:1.4

(N20:4)

M0:1.18

(N20:18)

Datalink B1

M0:1.5

(N20:5)

M0:1.19

(N20:19)

Datalink B2

M0:1.6

(N20:6)

M0:1.20

(N20:20)

Datalink C1

M0:1.7

(N20:7)

M0:1.21

(N20:21)

Datalink C2

M0:1.8

(N20:8)

M0:1.22

(N20:22)

Datalink D1

M0:1.9

(N20:9)

M0:1.23

(N20:23)

Datalink D2

M0:1.10

(N20:10)

M0:1.24

(N20:24)

Parameter Protocol Word #1

M0:1.11

(N20:11)

M0:1.25

(N20:25)

Parameter Protocol Word #2

M0:1.12

(N20:12)

M0:1.26

(N20:26)

Parameter Protocol Word #3

M0:1.13

(N20:13)

M0:1.27

(N20:27)

Parameter Protocol Word #4

0007

COP

Copy File
Source

#N20:0

Dest

#N21:0

Length

28

COP

XMIT Data
Word 0

PROFIBUS scanners vary from manufacturer to manufacturer in how the bytes are ordered in a word. For example, some PROFIBUS
scanners operate with high & low bytes swapped (the value "1234" is represented as "3412"). The WRITE data is copied into
N21: and the bytes are reversed in the SWP instruction below so a value such as "3412" is viewed as "1234".

N21: contains the actual write data that is being sent to the PROFIBUS scanner.

0008

SWP

Swap
Source

#N21:0

Length

28

SWP

XMIT Data
Word 0