Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 93

Advertising
background image

Troubleshooting the PROFIBUS Module and Network

8-3

8.1.2 MS Status Indicator

Table 8.2 – MS Status Indicator: State Definitions

Status

Cause

Corrective Action

Off

The module is not
powered.

Securely connect the module
to the SP600 drive using the
ribbon cable.

Apply power to the drive and
network.

Flashing
Red

The module has
failed the firmware
test.

Cycle power to the drive.
Parameter settings may have
been changed.

Clear faults in the module.

If cycling power does not
correct the problem, the
parameter settings may have
been corrupted. Reset defaults
and reconfigure the module.

If resetting defaults does not
correct the problem, flash the
module with the latest firmware
release.

Solid
Red

The module has
failed the hardware
test.

Cycle power to the drive.

Replace the module.

Flashing
Green

The module is
operational but is not
transferring I/O data.

Place the scanner in RUN
mode.

Configure the module for the
program in the controller.

Program the controller to
recognize and transmit I/O to
the module.

Solid
Green

The module is
operational and
transferring I/O data.

No action.