2 configuring the sst-pfb-slc profibus scanner – Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 37

Advertising
background image

Configuring the PROFIBUS Scanner

5-5

5.2

Configuring the SST-PFB-SLC
PROFIBUS Scanner

The following steps are performed to configure the SST-PFB-SLC
scanner using the SST PROFIBUS Configuration Software Tool. In
our example, the PROFIBUS network will consist of a SLC master
and two SP600 drives. The ladder examples in the manual will use
the following configuration:

Logic Command / Status and Reference / Feedback enabled

Datalink A enabled

Datalink B enabled

Datalink C enabled

Datalink D enabled

Parameter Access enabled (used to perform explicit messaging)

The SLC processor must be in Program mode to configure the
scanner.

Step 1.

Click on the (+) sign of the Masters folder in the Library
window to open the SST sub-folder. Available DP masters
are displayed in this sub-folder.

Step 2.

Click on the (+) sign of the Slaves folder in the Library
window and the Reliance Electric sub-folder to display
the available DP slaves or the RECOMM-PBUS slave.
Refer to figure 5.7.

Step 3.

Double-click the SST-PFB-SLC MASTER in the Masters
folder in the Library window to add the scanner to the
network.