Rockwell Automation RECOMM-PBUS PROFIBUS Communications Module User Manual

Page 83

Advertising
background image

Using Explicit Messaging (Parameter Protocol)

7-9

Write Examples

Request

Response

RC

“2” (‘0010’ binary) to write a 8-bit or 16-bit
parameter
“3” (‘0011 binary) to write a 32-bit parameter

RC

“1” (0001’) Transferring a 8-bit or 16-bit
parameter value
“2” (‘0010’) Transferring a 32-bit parameter
value
“7” (‘0111’) Request rejected (including fault
number)

SPM

Not used

SPM

Not Used

PNU

Parameter number being written

PNU

Confirms the parameter number (equals the
PNU from the request)

Subindex

Selects which DPI port to talk to (“0”= DPI
Hosts “5”= RECOMM-PBUS on SP600
drives)

Subindex

Confirms the DPI port (equals the Subindex
from the request)

Parameter value high

Contains the high word if writing a 32-bit
parameter

Parameter value high

Confirms the high word if writing a 32-bit
parameter.

Parameter value low

Contains the write value for a 8-bit or 16-bit
parameter, or the low word if writing a 32-bit
parameter

Parameter value low

Confirms the write value for a 8-bit or 16-bit
parameter, the low word (if writing a 32-bit
parameter, or the fault code (if RC=”7”)

Bit 15-12

11

10-0

15-12

11

10-0

Parameter Access
Word 1
(PCA)

RC

SPM

PNU

RC

SPM

PNU

Parameter Access
Word 2
(IND)

Subindex

Subindex

Parameter Access
Word 3
(PVA)

Parameter value high

(32 bit high word)

Parameter value high

(32 bit high word)

Parameter Access
Word 4
(PVA)

Parameter value low

(32-bit low word/

or 8-bit/16-bit value)

Parameter value low

(32-bit low word/

or 8-bit/16-bit value)

Request

Response

Advertising