Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual

Page 108

Advertising
background image

Control Primer

7-6


The advantages of the proportional action are: it is simple, easy to tune, and has a rapid response.
The disadvantage is that it has an offset.

Using the expression in Figure 7-2 and substituting e with expression 7-1 yields the expression for m
the manipulated output:


m = K ( r - c ) + b

(7-3)



Figure 7-3 is an example of how the offset can be shown by repeatedly solving for the manipulated
controller output (m) in expression 7-3. Let the setpoint (r) change from 0 to 0.23, gain (K) = 0.5,
bias (b) = 0, and c

n

= m

n-1

.

Figure 7-2

Proportional (P)
Control Action