Two-wire transmitter, Analog current input, Analog voltage input – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual

Page 35: Hardware installation/maintenance 3-13

Advertising
background image

Hardware Installation/Maintenance

3-13

Wiring and Jumper Placement for T6200C
Channels 9-16

Two-Wire Transmitter

This wiring and jumper
placement is normally used
with isolated two-wire
transmitters where the
transmitter power is
supplied by the Controller.
Refer to Figure 2-3.

Factory

Default

1

4-20 mA

Two-Wire

Transmitter

(Isolated)

+

-

24 Vdc
Supply

mA Input

(reference to

common

through resistor)

+

-

T6200C Controller

SHLD

Analog Current Input

This wiring and jumper
placement is normally used
with four-wire current
transmitters when the power
is not supplied by the
Controller. Refer to Figure
2-2.

4-20 mA

Transmitter

+

-

mA Input

(Isolated from

common)

+

-

T6200C Controller

1

Power

Source

Transmitter output

may be referenced

to common

SHLD

Analog Voltage Input

This wiring and jumper
placement is for voltage
inputs. Refer to Figure 2-1.

DC Voltage
Transmitter

+

-

+

-

T6200C Controller

Power

Source

Transmitter output

may be referenced

to common

DC Voltage Input

(Isolated from

common)

1

SHLD

Advertising