Two-wire transmitter, Analog current input, Analog voltage input – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual
Page 35: Hardware installation/maintenance 3-13

Hardware Installation/Maintenance
3-13
Wiring and Jumper Placement for T6200C
Channels 9-16
Two-Wire Transmitter
This wiring and jumper
placement is normally used
with isolated two-wire
transmitters where the
transmitter power is
supplied by the Controller.
Refer to Figure 2-3.
Factory
Default
1
4-20 mA
Two-Wire
Transmitter
(Isolated)
+
-
24 Vdc
Supply
mA Input
(reference to
common
through resistor)
+
-
T6200C Controller
SHLD
Analog Current Input
This wiring and jumper
placement is normally used
with four-wire current
transmitters when the power
is not supplied by the
Controller. Refer to Figure
2-2.
4-20 mA
Transmitter
+
-
mA Input
(Isolated from
common)
+
-
T6200C Controller
1
Power
Source
Transmitter output
may be referenced
to common
SHLD
Analog Voltage Input
This wiring and jumper
placement is for voltage
inputs. Refer to Figure 2-1.
DC Voltage
Transmitter
+
-
+
-
T6200C Controller
Power
Source
Transmitter output
may be referenced
to common
DC Voltage Input
(Isolated from
common)
1
SHLD