T6200 analog input fb – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual

Page 147

Advertising
background image

Configuration

8-27


Function Blocks

:

The name of the operation or function, or the type of function block is written within the block
rectangle (such as K_sll below). In case of a function block call, the name of the called instance
must be written upon the block rectangle.

The data flow may represent values of any data type. All connections must be between input and
outputs points having the same data type

T6200 Analog Input FB

Analog Input Block Editing

:

Analog Input Parameter Adaptation: Verify all AI parameters to make sure that they meet the

requirements of your application.

-

The Channel number to which the analog input is connected to

-

The Input signal type (20= 4-20 mA)

-

The Filter requirements of the analog input signal, if any

-

The Linearization, Linear or Square Root (do not select square root for h or hd inputs!)

-

The Transmitter range of analog input in Engineering Units


If special linearization, oscillation monitoring, etc is required, specify AI_C in place of AI.

FIGURE 8-14


AI Function Block

FIGURE 8-13

Function Block
Name and Type