Hardware Installation/Maintenance

3-15

Frequency Inputs

This wiring and jumper
placement is for a
frequency/pulse
preamplifier input with
the Controller supplying
the power (Channel 22,31
and 32).

Frequency/Pulse

Preamplifier or other

Discrete Device

+

-

24 Vdc
Supply

Discrete

Input

T6200C Controller

(Circuit Common)

PWR

OUT

COM

SHLD

1

0-25KHz only for

Channels 22, 31 &

32

Discrete Outputs with Internal Power

This wiring and jumper
placement is for discrete
(On/Off) outputs. The
Controller supplies 24
VDC power for the 20
mA max load. Load
Example: Entrelec RB
131 (010055.23) relay.
Refer to Figure 2-7.

Discrete

Load

<20 mA

+

-

+

-

Discrete Output
(Open Collector

Transistor)

T6200C Controller

1

24 Vdc
Supply

+

-

Discrete Outputs with External Power

This wiring and jumper
placement is for discrete
(On/Off) outputs. The
power source (less than 38
VDC) is external. The
discrete load is 0.25 Amp
max. Refer to Figure 2-8.

Discrete

Load

<0.25 A

+

-

+

-

Discrete Output
(Open Collector

Transistor)

T6200C Controller

1

Circuit

Common

+

-

Power Source

<38 Vdc

+

-