Frequency inputs, Discrete outputs with internal power, Discrete outputs with external power – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual
Page 37: Hardware installation/maintenance 3-15

Hardware Installation/Maintenance
3-15
Frequency Inputs
This wiring and jumper
placement is for a
frequency/pulse
preamplifier input with
the Controller supplying
the power (Channel 22,31
and 32).
Frequency/Pulse
Preamplifier or other
Discrete Device
+
-
24 Vdc
Supply
Discrete
Input
T6200C Controller
(Circuit Common)
PWR
OUT
COM
SHLD
1
0-25KHz only for
Channels 22, 31 &
32
Discrete Outputs with Internal Power
This wiring and jumper
placement is for discrete
(On/Off) outputs. The
Controller supplies 24
VDC power for the 20
mA max load. Load
Example: Entrelec RB
131 (010055.23) relay.
Refer to Figure 2-7.
Discrete
Load
<20 mA
+
-
+
-
Discrete Output
(Open Collector
Transistor)
T6200C Controller
1
24 Vdc
Supply
+
-
Discrete Outputs with External Power
This wiring and jumper
placement is for discrete
(On/Off) outputs. The
power source (less than 38
VDC) is external. The
discrete load is 0.25 Amp
max. Refer to Figure 2-8.
Discrete
Load
<0.25 A
+
-
+
-
Discrete Output
(Open Collector
Transistor)
T6200C Controller
1
Circuit
Common
+
-
Power Source
<38 Vdc
+
-