T6200 controller electrical power wiring – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual
Page 28

Hardware Installation/Maintenance
3-6
T6200 Controller Electrical Power Wiring
The guidelines below should be followed when wiring the power to the T6200 Controller:
The maximum wire size is 16 AWG stranded.
All wiring should be multi-stranded annealed copper with insulation that meets the
requirements of all applicable electrical codes.
AC power wiring should be run in a separate conduit from the T6200 Controller power and the
I/O.
The stripped portion of the wire should be 3/16” (5 mm) long.
Wires should be inserted in the clamp type terminals until they touch the internal stops. The
terminal screw should be tightened while holding the wire in place. Check for proper clamp
pressure with a gentle tug on the wire.
Electrical power should be provided from a redundant, highly reliable, dedicated 26 Vdc power
source.
Power consumption is 15 watts for the T6200 Controller and 15 watts for the Operator
Interface, not including field devices.
The T6200 Controller has redundant 26 Vdc power supply connections.