Modbus Interface – RS-232/RS-485

B-4

<m-bits>

Maximum number (1..2000) of coils or inputs to poll
with one message.

<m-regs>

Maximum number (1...125) of registers to poll with
one message.

OFFSET

Difference between point number and on-the-wire
address. (Modicon specifies 1)

PRIORITY

Unit priority scan. Default priority is 1. Place only a
small number of high priority points at priority zero.

RETRY

Retry count and optional interval. Interval defines the
expected response time of the unit.

Table 1 Polling Parameter Values


The default polling parameters are:

“@ 3

GAP 0 0 MAX 16 10 OFFSET 1
RETRY 10 / 1 PRIORITY 1”

The lowest numbered priorities take precedence over higher numbered priorities. In order to
insure that all points cannot possibly be scanned as frequently as specified, the priority scan is
cascaded: Whenever a priority level is completed, at lease one poll will be performed at the next
level even if it is already time to poll a higher priority block.

<unit>

UNIT {1..247}[=<unit-tag>][<poll-parm>] points>…

<points> <address>

{[<scale>]<tag-def>}…

<address> <coil/input-nr>
<scale>

{“+” | “-“} [“:” [[“-“] <bits>]]
[H [, L[, h[, I]]]]

<bits>

{-15.. 16, 32}

Table 2 UNIT Directive


The UNIT directive introduces each MODBUS unit. Units may be numbered from one to 247
according to the MODBUS specification. The optional <unit-tag> is reserved for the future
reporting of off-line unit alarms. Most of the polling parameters, <poll-parm>, apply only to
MODBUS masters. The specific syntax depends upon the <protocol> selection.

The <points> define global tags and assign MODBUS addresses to them in the current unit and
port. Once an address is specified, tags will be assigned successive addresses until a new starting
address is specified. Multiple tags may not be assigned to a single address. Use a comma to
separate point tag names only if a break in polling messages is required there; otherwise separate
tag names with a space. The values of tags can be shared with the reserve controller over the
backup link: prefix the tag name with ‘&’ to include it in backup data sent from the active to the
reserve controller. Subsequent tags will also be sent to backup until a comma delimiter or a new
address.

MODBUS <coil/input-nr> specify the corresponding remote data type. Coils and inputs are
discretes which can only be assigned to U-32 Boolean tags. Input and holding registers are sixteen
or thirty-two bit integers which can be assigned to any data type. If no data type is otherwise
specified for a controller tag, it defaults to the type of the remote point.

00001..09999

1

Coils

10001..19999 Discrete

inputs

30001..39999 Input

registers

40001..49999 Holding

registers


Table

3 <coil/input-nr>

1

Since the first digit of <coil/input-nr> specifies the MODBUS data-type, intervening leading

zeros may be omitted. For example “00001” may be written “01” for the first coil and “40001”
may be written “41” for the first holding register.