3-14

Discrete Inputs with Excitation from Controller

This wiring and jumper
placement is for discrete
(On/Off) inputs. The
Controller supplies 24 VDC
power for the input. Refer to
Figure 2-6.

Contact

+

-

Discrete Input

(24 Vdc/5 mA

excitation)

Circuit

Common

T6200C Controller

Alternate

Open Collector

Transistor

1

Isolated Discrete Inputs

This wiring and jumper
placement is for discrete
(On/Off) inputs. The
discrete inputs are isolated
from other circuits and the
external power for the input
is either 18-32 Volt AC or
DC. Refer to Figure 2-5.

Power Source

18 V to 32 V

ac/dc

+

-

Contact

+

-

Discrete Input

(Optically

coupled)

T6200C Controller

1

Polarity

Arbitrary


Wiring and Jumper Placement for T6200C
Channels 17-22, 31, and 32

Discrete Inputs with Excitation from Controller

This wiring and jumper
placement is for discrete
(On/Off) inputs. The
Controller supplies 24
VDC power for the input.
Refer to Figure 2-6.

Contact

+

-

Discrete Input

(24 Vdc/5 mA

excitation)

Circuit

Common

T6200C Controller

Alternate

Open Collector

Transistor

Factory

Default

1

Isolated Discrete Inputs

This wiring and jumper
placement is for discrete
(On/Off) inputs. The
discrete inputs are isolated
from other circuits and the
external power for the
input is either 18-32 Volt
AC or DC. Refer to
Figure 2-5.

Power Source

18 V to 32 V

ac/dc

+

-

Contact

+

-

Discrete Input

(Optically

coupled)

T6200C Controller

Polarity

Arbitrary

1

Advertising