6-25
Surge Curve Screens
-
Surge Curve Configuration: The Surge Limit Line (SLL) is arranged in a lookup table format
with linear vector interpolation. Up to 20 points can be defined. The X points define the domain
input – Hp,sim. The Y points define the range (output) – Q2,sim.
-
Click on Edit Mode Enable check. Drag the surge points to the desired position or use the
Up/Down buttons to position the surge points.
FIGURE 6-20
Surge Curve-
Op Point Display:
X/Y Map
SLL Configuration
below