Hardware Installation/Maintenance

3-3







Hardware

Installation/Maintenance




`

Site Selection Considerations


The T6200 Controller requires following conditions during normal operation:

ƒ 32 to 122º F (0 to 50º C)

ƒ 5 to 96% Relative humidity

ƒ Protection from direct contact with water, chemicals, and conductive dust.

ƒ Protection from exposure to sulfur compounds, acid, other corrosive or reactive vapors or

fumes, dust, and lint.


For estimating heat load requirements, the T6200 Controller dissipates a maximum of 10 BTU/hr.
(or 24 KGM-CAL/Hr) to the inside of the control panel.

Access Considerations


There are very few restrictions on the mounting position of the T6200 Controller. The following should
be taken into consideration:

ƒ

All electrical power and input/outputs are connected on the rear termination panel.

Because as many as 70 conductors and four cables can be terminated to each T6200 Controller
adequate wireway space should be provided.

ƒ

The T6200 Controller is operated from the front of the unit with switches on the

bottom. The Operator Interface slides up 0.5 in. (12 mm) to remove.