Hardware installation/maintenance, Site selection considerations, Access considerations – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual
Page 25

Hardware Installation/Maintenance
3-3
Hardware
Installation/Maintenance
`
Site Selection Considerations
The T6200 Controller requires following conditions during normal operation:
32 to 122º F (0 to 50º C)
5 to 96% Relative humidity
Protection from direct contact with water, chemicals, and conductive dust.
Protection from exposure to sulfur compounds, acid, other corrosive or reactive vapors or
fumes, dust, and lint.
For estimating heat load requirements, the T6200 Controller dissipates a maximum of 10 BTU/hr.
(or 24 KGM-CAL/Hr) to the inside of the control panel.
Access Considerations
There are very few restrictions on the mounting position of the T6200 Controller. The following should
be taken into consideration:
All electrical power and input/outputs are connected on the rear termination panel.
Because as many as 70 conductors and four cables can be terminated to each T6200 Controller
adequate wireway space should be provided.
The T6200 Controller is operated from the front of the unit with switches on the
bottom. The Operator Interface slides up 0.5 in. (12 mm) to remove.