T6200 – analog output definition – Rockwell Automation T6200 Compressor Anti-Surge and Capacity Controller User Manual
Page 152

Configuration
8-32
T6200 – Analog Output Definition
-
Analog Output Block Editing
:
Analog Output Parameter Adaptation: Verify all AO parameters to make sure that they meet the
requirements of your application.
-
The Channel number to which the analog output is connected to
-
The Output signal type (1= 4-20 mA)
-
The Output display indication, AO_Dis: 0= Direct indication (air to open); 1= Reverse
indication (air to close)
-
The Lower bound (in percent) for the output, OPLOLM: Normally 0
-
The Upper bound (in percent) for the output, OPHILM: Normally 100
-
The max. Decreasing Rate (in % per sec), OPNR.M: Normally 100
-
The max. Increasing Rate (in % per sec), OPPR.M: Normally 100
-
The Recall of the old output value, Recall: 0= Start with zero; 1= Start at old value; 2=
Same as PID in this loop (default)
FIGURE 8-21
AO FB Configuration